WDR-60-24 DIN-Rail Power Supply, 180~550 VAC to 24 VDC/2.5 A, 60 W
60 W DIN-rail power supply with an ultra-wide 180~550 VAC input for single or 2-phase systems, delivering 24 VDC/2.5 A across a -30 ~ +85 °C operating range.
- 180 ~ 550 VAC ultra-wide input for single-phase or 2-phase systems
- 60 W rated power, 24 VDC at 2.5 A, 89% efficiency
- Slim 32 mm metal DIN-rail housing with free air convection cooling
- Operating temperature -30 ~ +85 °C, with derating above +60 °C
- 4.7 KVac I/O isolation (reinforced) and over voltage category III
- Protections against short circuit, overload, over voltage and over temperature
853,12 kr per st.
| 1–9 st. | 853,12 kr | |
|---|---|---|
| 10–30 st. | 819,88 kr | −4 % |
| 31+ st. | 808,80 kr | −5 % |
Produktinformation "WDR-60-24 DIN-Rail Power Supply, 180~550 VAC to 24 VDC/2.5 A, 60 W"
WDR-60-24 CR is a 60 W DIN-rail power supply for industrial panels where the mains supply varies widely. Its 180 ~ 550 VAC input suits single-phase or 2-phase systems, so one unit can cover a broad range of supply conditions without a separate variant for each voltage.
The 32 mm slim metal housing mounts on TS-35/7.5 or TS-35/15 rails and is cooled by free air convection. The 24 VDC output is adjustable between 31 ~ 37 V, with a DC OK relay contact for signalling the output status and protection against short circuit, overload, over voltage and over temperature. The unit is rated for Over voltage category III.
The 4.7 KVac reinforced I/O isolation and ±1.0% voltage tolerance make it a practical choice for automation, surveillance and telecommunication equipment. Operation is rated up to +85 °C with derating above +60 °C, and it is also rated for operation at 2000 m altitude.
Applications
- Industrial automation
- Surveillance
- Telecommunication
| Product type: | Power supply |
|---|---|
| Isolation: | 4.7 KVac |
| Power input: | 180 ~ 550 VAC |
| Operating temperature: | -30 ~ +85 °C |
| Mounting: | DIN-rail |
| Housing: | Metal |
Specifikationer
| Safety | |
|---|---|
| Standard | UL61010 approved, EN61558-2-16, EAC TP TC 004 approved; design refer GL and EN60204-1(By request) |
| EMC | |
| Standard | Compliance to EN55011, EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2 Class A, EN61000-3-3 EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN55035, EN61000-6-2, EN61204-3, heavy industry level, criteria A |
| Input | |
| Voltage Range | 180 ~ 550 VAC 254 ~ 780 VDC |
| Frequency Range | 47 ~ 63 Hz |
| Inrush Current (Typ.) | COLD START 30 A/230 VAC 50 A/400 VAC |
| Leakage Current | <2 mA / 530 VAC |
| Output | |
| Ripple & Noise (Max.) | 150mVp-p |
| Voltage Adj. Range | 31 ~ 37 V |
| Voltage Tolerance | ±1.0% |
| Linearity | ±0.5% |
| Load Regulation | ±0.5% |
| Setup, Rise Time | 1000ms, 70ms, 20ms/400 VAC 2000ms, 70ms, 10ms/230 VAC at full load |
| DC Voltage | 24 V |
| Rated Power | 60 W |
| Rated Current | 2.5 A |
| Efficiency | 89% |
| Protection | |
| Over Voltage | 31 ~ 37V Protection type : Shut down o/p voltage, re-power on to recover |
| Overload | 105 ~ 135% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed |
| Function | |
| DC OK Active Signal (Max.) | 30V/1A resistive |
| Mechanical | |
| Casing | Metal |
| Dimensions (mm) | (32 * 125.2 * 102) mm |
| Environment | |
| Operating Temperature | -30 ~ +85°C |
| Storage Temperature | -40 ~ +85°C |
| Humidity | 20 ~ 90% RH non-condensing |
Specifikationer enligt tillverkaren. Ändringar förbehålls.