SG-3016-80-G Strain Gauge Signal Conditioner, 80 Hz Low Pass, mV to V/mA
Strain gauge input signal conditioner converting ±10 to ±100 mV inputs to ±5/±10 V, 0 ~ 5/10 V or 0 ~ 20 mA outputs, with 1000 VDC three-way isolation.
- Three-way isolation of input, output and power: 1000 VDC
- Accuracy of ±0.1% of full range
- Input and output ranges set through internal configuration switches
- Three VRs (Zero, Span, Exci) for calibrating input and output accuracy
- Bandwidth typically 80 Hz, specified as <80 Hz
- Excitation voltage output 0 ~ +10 VDC, max. load current +20 mA
2 204,82 kr per st.
| 1–9 st. | 2 204,82 kr | |
|---|---|---|
| 10–30 st. | 2 138,34 kr | −3 % |
| 31+ st. | 2 094,03 kr | −5 % |
Produktinformation "SG-3016-80-G Strain Gauge Signal Conditioner, 80 Hz Low Pass, mV to V/mA"
The SG-3016-80-G CR is a signal conditioning module that takes a millivolt-level voltage input and delivers a voltage or current output for the rest of the control system. It suits engineers who need to condition strain gauge type signals on a DIN-rail without building a custom interface.
Input and output ranges are selected through internal configuration switches, so the same module can be matched to different sensor spans and controller inputs. Three VRs (Zero, Span and Exci) allow the accuracy of the input and output range to be calibrated, and an LED shows whether the module is functioning correctly. The typical bandwidth is 80 Hz.
Three-way isolation of 1000 VDC separates input, output and power, and the module operates from a +10 ~ +30 VDC supply with reverse polarity protection. The -G variant is listed with the RoHS-compliant strain gauge signal conditioner description.
Applications
- Strain gauge signal conditioning
- Converting low-level millivolt sensor signals to standard voltage or current outputs
- Isolated signal conditioning in industrial control panels
| Product type: | Signal conditioner |
|---|---|
| Isolation: | 1000 VDC |
| Power input: | +10 ~ +30 VDC |
| Operating temperature: | -25 ~ +75 °C |
| Mounting: | DIN-rail |
Specifikationer
| Isolation | |
|---|---|
| Three-way Isolation | 1000 VDC |
| Analog Input | |
| Channels | 1 |
| Type | ±10 mV, ±20 mV, ±30 mV, ±50 mV, ±100 mV |
| Accuracy | ±0.1% of full range |
| Bandwidth | <80 Hz |
| Analog Output | |
| Channels | 1 |
| Range | Voltage: ±5 VDC, ±10 VDC, (Note 1: Only supports Bipolar-type input) 0 ~ 5 VDC, 0 ~ 10 VDC (Note 2: Only supports Unipolar-type input) Current: 0 ~ 20 mA (Note 2: Only supports Unipolar-type input) |
| Current Load Resistance | 0 ~ 500 Ω (Source) |
| Excitation Voltage Output | |
| Channels | 1 |
| Range | 0 ~ +10 VDC |
| Max. Load Current | +20 mA |
| Power | |
| Reverse Polarity Protection | Yes |
| Input Range | +10 ~ +30 VDC |
| Consumption | 1.44 W (Voltage Output), 1.74 W (Current Output) |
| Mechanical | |
| Dimensions (mm) | 25 mm x 114 mm x 70 mm (W x L x H) |
| Environment | |
| Operating Temperature | -25 °C ~ 75 °C |
| Storage Temperature | -30 °C ~ 75 °C |
| Humidity | 5 ~ 95%, non-condensing |
Specifikationer enligt tillverkaren. Ändringar förbehålls.
Nedladdningar