SDR-120-12 DIN-Rail Power Supply, 88~264 VAC to 12 VDC/10 A, 120 W
120 W DIN-rail power supply converting 88~264 VAC to a 12 VDC/10 A output, with active PFC, a built-in DC OK relay contact and a metal casing.
- 120 W rated power with 12 VDC / 10 A output and 150% peak load capability
- Wide 88~264 VAC input range with active PFC, PF>0.93
- Built-in DC OK relay contact for status monitoring
- Output adjustable from 12 to 14 V
- Protections against short circuit, overload, over voltage and over temperature
- Metal casing, free air convection cooling, mounts on TS-35/7.5 or TS-35/15 DIN rail
1 684,08 kr per st.
| 1–9 st. | 1 684,08 kr | |
|---|---|---|
| 10–30 st. | 1 628,69 kr | −3 % |
| 31+ st. | 1 595,45 kr | −5 % |
Produktinformation "SDR-120-12 DIN-Rail Power Supply, 88~264 VAC to 12 VDC/10 A, 120 W"
The SDR-120-12 CR is a 120 W DIN-rail power supply that converts a wide 88~264 VAC input into a regulated 12 VDC output rated at 10 A. It suits engineers who need a compact, efficient supply for industrial control panels, with protection against short circuit, overload, over voltage and over temperature.
Active power factor correction (PF>0.93) keeps the input current draw clean, and the unit tolerates 150% peak load. The output voltage can be adjusted between 12 and 14 V, and a built-in DC OK relay contact lets the controller monitor supply status.
The metal casing is cooled by free air convection and mounts on TS-35/7.5 or TS-35/15 DIN rail. The unit is UL 508 approved for industrial control equipment, meets EN61000-6-2 industrial immunity levels, and carries CE, UKCA, RoHS and WEEE marks. Each unit undergoes a 100% full load burn-in test.
Applications
- Industrial control equipment
- Industrial control panels and DIN-rail mounted automation systems
- Heavy industry environments
| Product type: | Power supply |
|---|---|
| Relay outputs: | 1 |
| Power input: | 88~264 VAC |
| Operating temperature: | -25 ~ +70 °C |
| Mounting: | DIN-rail |
| Housing: | Metal |
Specifikationer
| Safety | |
|---|---|
| Standard | UL508, TUV EN60950-1 approved |
| EMC | |
| Standard | Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3, EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, SEMI F47, GL approved |
| Input | |
| Voltage Range | 88 ~ 264 VAC 124 ~ 370 VDC |
| Frequency Range | 47 ~ 63Hz |
| AC Current (Typ.) | 1.4 A/115 VAC 0.7 A/230 VAC |
| Inrush Current (Typ.) | 35 A/115 VAC 70 A/230 VAC |
| Leakage Current | <1 mA/240 VAC |
| Output | |
| Ripple & Noise (Max.) | 100mVp-p |
| Voltage Adj. Range | 12 ~ 14V |
| Voltage Tolerance | ±1.0% |
| Linearity | ±0.5% |
| Load Regulation | ±1.0% |
| Setup, Rise Time | 1500ms, 60ms/230 VAC 3000ms, 60ms/115 VAC at full load |
| Hold Up Time (Typ.) | 20ms/230 VAC 20ms/115 VAC at full load |
| DC Voltage | 12 V |
| Rated Power | 120 W |
| Rated Current | 10 A |
| Efficiency | 89% |
| Protection | |
| Over Voltage | 14 ~ 17V Protection type : Shut down o/p voltage, re-power on to recover |
| Overload | Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage >150% rated power, constant current limiting with auto-recovery within 3 seconds and shut down o/p voltage after 3 seconds |
| Function | |
| DC OK Active Signal (Max.) | 60 VDC/0.3A, 30VDC/1A, 30VAC/0.5A resistive load |
| Mechanical | |
| Casing | Metal |
| Dimensions (mm) | (63 * 125.2 * 113.5)mm |
| Environment | |
| Over-temperature Protection | 95°C ±5°C (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down |
| Temperature Coefficient | ±0.03%/°C (0 ~ 50°C) |
| Operating Temperature | -25 ~ +70°C (Refer to "Derating Curve") |
| Storage Temperature | -40 ~ +85°C |
| Humidity | 20 ~ 95% RH Non-condensing |